DOE PG12 refers to Combustion of Fuel manufactured from or comprised of Solid Waste in appliances between 0.4 and 3 MW thermal input. The Clean Air Act applies to smaller installations.
All pollutant concentrations should be expressed at reference conditions 273K, 101.3 kPa and 11% Oxygen.
PG12 Is currently being reviewed, but O2, CO and particulates measurement is required as below.
Limits to emissions are :
o Total particulate matter 200mg/m3. Should be continuously monitored.
o Carbon Monoxide new: Limit values < 1 MW 250 mg/m3 , > 1MW 150 mg/m3 for non continuous monitoring .
o Where monitoring is continuous 95%of 15 minute average for each rolling 24 hour period not to exceed the emission limit values and the peak values not to exceed twice the limit values.
o For fuller information requirements for larger plant and for advice on analytical and datalogging equipment please contact us